Print Back
Temp Control, DIN W48XH96mm, 1 Alarm, Relay Contact Output, 100-240VAC
Unit of Measure

Specifications

Brands

N/A Autonics USA

Width

N/A 48 mm

Height

N/A 96 mm

Dimensions

N/A 48 x 96 mm

Alternating Current (AC) Voltage

N/A 100 to 240 V

Control Method

N/A On/Off Control, P, PI, PD, PID Control

Sampling Cycle

N/A 50 ms

Protection Structure

N/A Ingress Protection (IP) 65 (Front Panel)

Control Output

N/A Relay Contact Output

Approval

N/A Canadian and US Standards by Underwriters' Laboratories (CURUS) European Conformity (CE)

Environment Ambient Temperature

N/A -10 to 50 ºC

Environment Storage Temperature

N/A -20 to 60 ºC

Environment Ambient Relative Humidity (RH)

N/A 35 to 85 %

Environment Storage Relative Humidity (RH)

N/A 35 to 85 %

Display Method

N/A 4-Digit 7-Segment Light Emitting Diode (LED)

Thermocouple Input Specification

N/A B(PR) C(TT) E(CR) G(TT) J(IC) K(CA) L(IC) N(NN) Platinel II R(PR) S(PR) T(CC) U(CC)

Resistance Temperature Detector (RTD) Input Specification

N/A Cu100Ω Cu50Ω DPt100Ω DPt50Ω JPt100Ω Nickel 120Ω

Analog Input Specification

N/A 0 to 100mV 0 to 10V 0 to 20mA 0 to 5V 1 to 5V 4 to 20mA

Proportional Band

N/A 0.1 to 999.9ºC/ºF(0.1 to 999.9%)

Integral Time Range

N/A 0 to 9999 s

Derivative Time

N/A 0 to 9999 s

Type

N/A High Accuracy

Option Output

N/A Alarm 1

Alarm Output

N/A Alarm1

Insulation Type

N/A Double Insulation or Reinforced Insulation (Dielectric Strength Between the Measuring Input Part and the Power Part: 2kV)

Control Output 1

N/A Relay (250VAC to 3A)

Display Accuracy Resistance Temperature Detector (RTD)

N/A
  • At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit
  • Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit

Display Accuracy Thermocouple

N/A
  • At room temperature(23℃±5℃):(PV ±0.3% or ±1℃, select the higher one) ±1-digit
  • Out of room temperature:(PV ±0.5% or ±2℃, select the higher one) ±1-digit

Analog Display Accuracy

N/A
  • At room temperature(23℃±5℃): ±0.3% F.S. ±1-digit
  • Out of range of room temperature: ±0.5℃% F.S. ±1-digit

CT Input Display Accuracy

N/A ±5% F.S. ±1-Digit

Hysteresis (Adjustable Sensitivity)

N/A RTD/Thermocouples: 1 to 100ºC/ºF(0.1 to 100.0ºC/ºF) Variable Analog: 1 to 100-Digit

Manual Reset

N/A 0.0 to 100.0%

Option Input

N/A CT, Digital(DI-1)

Shipping Weight

N/A 141 g

Unit Weight

N/A 211 g

Weight

N/A 0.53 lb

Note

N/A
  • S" represents SSR drive output support models which SSRP function (standard ON/OFF control, cycle control, phase control) are available.
  • "C" represents selectable current and SSR drive output support models.
  • Select "R" or "C" type in case of using heating and cooling control and "N" type in case of using standard control.
  • CT input of TK4N is available only for the standard model which has alarm output 1.
  • Display accuracy:
  • At room temperature (23?±5?)
  • Thermocouple K, J, T, N, E type, below -100?/Thermocouple L, U, PL? type, RTD Cu50?, DPt50?: (PV ±0.3% or ±2?, select the higher one) ±1-digit
  • Thermocouple C, G, R, S type, below 200?: (PV ±0.3% or ±3?, select the higher one) ±1-digit
  • Thermocouple B type, below 400?: there is no accuracy standards.
  • Out of room temperature range
  • RTD Cu50?, DPt50?: (PV ±0.5% or ±3?, select the higher one) ±1-digit
  • Thermocouple R, S, B, C, G type: (PV ±0.5% or ±5?, select the higher one) ±1-digit
  • Others, Below -100?: within ±5?
  • In case of TK4SP Series, ±1? will be added to the degree standard.
  • The weight includes packaging. The weight in parenthesis is for unit only.
  • Environment resistance is rated at no freezing or condensation.