Print Back
Advanced Multi-Channel Modular Temperature Controller, 2 channel, CT Input, Digital Input(DI-1/2…
Unit of Measure

Specifications

Brands

N/A Autonics USA

Direct Current (DC) Voltage

N/A 24 V

Input Type Analog Voltage

N/A 0 to 100mVDC 0 to 10VDC 0 to 5VDC 1 to 5VDC

Input Type Analog Current

N/A 0 to 20mA 4 to 20mA

Control Method

N/A On/Off Control P PD PI PID Control

Sampling Cycle

N/A 50 ms

Note for Sampling Cycle

N/A (2-CH or 4-CH Synchronous Sampling)

Protection Structure

N/A Ingress Protection (IP) 20 (International Electrotechnical Commission (IEC) Standard)

Approval

N/A Canadian and US Standards by Underwriters' Laboratories (CURUS) European Conformity (CE) Korea Certification (KC)

Environment Ambient Temperature

N/A -10 to 50 ºC

Environment Storage Temperature

N/A -20 to 60 ºC

Environment Ambient Relative Humidity (RH)

N/A 35 to 85 %

Environment Storage Relative Humidity (RH)

N/A 35 to 85 %

Display Method

N/A None-parameter Setting and Monitoring is Available at External Devices (PC, PLC, etc.)

Thermocouple Input Specification

N/A B(PR) C(TT) E(CR) G(TT) J(IC) K(CA) L(IC) N(NN) Platinel II R(PR) S(PR) T(CC) U(CC)

Resistance Temperature Detector (RTD) Input Specification

N/A Cu100Ω Cu50Ω DPt100Ω DPt50Ω JPt100Ω Nickel 120Ω 3-wire type(permissible line resistance max. 5Ω)

Proportional Band

N/A RTD/Thermocouples: 1 to 999℃/ºF (0.1 to 999.9℃/ºF), analog: 0.1 to 999.9 digit

Integral Time Range

N/A 0 to 9999 s

Derivative Time

N/A 0 to 9999 s

Relay Output Control Period

N/A 0.1 to 120.0 s

SSR Output Control Period

N/A 1.0 to 120.0 s

Insulation Resistance

N/A 100MΩ (at 500VDC Megger)

Noise Immunity

N/A ±0.5kV the Square Wave Noise (Pulse Width: 1µs) By the Noise Simulator

Dielectric Strength

N/A 1000VAC 50/60Hz for 1 min (Between Input Terminals and Power Terminals)

Vibration

N/A 0.75mm Amplitude at Frequency of 5 to 55Hz (for 1 min) in Each X, Y, Z Direction for 2 Hours

Power Consumption

N/A 8

Insulation Type

N/A Double Insulation or Reinforced Insulation (Dielectric Strength Between the Measuring Input Part and the Power Part: 1kv)

Hysteresis (Adjustable Sensitivity)

N/A RTD/Thermocouples: 1 to 100ºC/ºF (0.1 to 100.0ºC/ºF), Analog: 1 to 100 Digit

Manual Reset

N/A 0 to 100%( 0.0 to 100.0%)

Allowable Rated Voltage Range

N/A 90 to 110 %

Control Output Relay

N/A 250VAC, 3A, 1a

Option Output Alarm

N/A 250VAC, 3A, 1a

Mechanical Relay Life Cycle

N/A Minimum 10000000 Operations

Electrical Relay Life Cycle

N/A Minimum 100000 Operations (250VAC, 3A Resistance Load)

Memory Protection

N/A Approximate 10 Years(Non-volatile Semiconductor Memory Type)

Maximum SSR Control Direct Current (DC) Voltage Output

N/A 12 V

SSR Control Direct Current (DC) Voltage Tolerance

N/A ±3 V

SSR Control Current Output

N/A 20 mA

Current Control Output

N/A Selectable Direct Current (DC) 4 to 20mA or Direct Current (DC) 0 to 20mA (Load Resistance Maximum 500Ω)

Number of Input Channels

N/A 2-Channel

Thermocouple Measurement Accuracy

N/A
  • At room temperature(23℃±5℃): (PV ±0.3% or ±1℃, higher one) ±1-digit
  • Out of room temperature range: (PV ±0.5% or ±2℃, higher one) ±1-digit

RTD Measurement Accuracy

N/A
  • At room temperature(23℃±5℃): (PV ±0.3% or ±1℃, higher one) ±1-digit
  • Out of room temperature range: (PV ±0.5% or ±2℃, higher one) ±1-digit

Analog Measurement Accuracy

N/A
  • At room temperature(23℃±5℃): ±0.3% F.S. ±1-digit
  • Out of room temperature range: ±0.5% F.S. ±1-digit

CT Input Option

N/A 0.0-50.0A (Primary Current Measurement Range), CT Ratio=1/1000, Measured Accuracy: ±5% F.S. ±1-digit

Communication Terminal

N/A RS485 Communication Output (Modbus RTU)

PC Loader Communication

N/A TTL

Option Digital Inputs

N/A Connect input: ON - max. 1kΩ, OFF - min. 100kΩ
Solid-state input: ON - max. residual voltage 0.9V, OFF - max. leakage current 0.5mA
Outflow current: approx. 0.3mA per input

Shipping Weight

N/A 177.7 g

Unit Weight

N/A 250.8 g

Weight

N/A 0.2 lb

Accessories

N/A Expansion Connector: 1 Module Lock Connector: 2

Note

N/A Thermocouple: Connecting 1 or more expansion module can vary measurement accuracy about ±1?, regardless of the number of connected expansion module.
Measured accuracy:
At room temperature (23?±5?)
  • Thermocouple K, J, T, N, E below -100?, L, U, PLII, and RTD Cu50?, DPt50?: (PV ±0.3% or ±2?, higher one) ± 1-digit
  • Thermocouple C, G and R, S below 200?: (PV ±0.3% or ±3?, higher one) ± 1-digit
  • Thermocouple B below 400?: there is no accuracy standards.
Out of room temperature range
  • RTD Cu50?, DPt50?: (PV ±0.5% or ±3?, higher one) ± 1-digit
  • Thermocouple R, S, B, C, G: (PV ±0.5% or ±5?, higher one) ± 1-digit
  • Other blow -100?: within ±5?
The weight includes packaging. The weight in parenthesis is for unit only.
Environment resistance is rated at no freezing or condensation.